(3) Brand New 3516C Diesel Generator Sets Rated 2000 kW

2007 CAT 3516C.bmp
 
2007 CAT 3516C.bmp
 
2006 CAT 3516B.bmp
 

(3) Brand New 3516C Diesel Generator Sets


Price: $0.00

Quantity:  
Catalog #:2024

(3) Brand New 3516C Diesel Generator Sets Rated 2000 kW, 480/277 Volt, 1800 RPM, 3 Phase, 60 Hertz, 4 Wire, 0.8 PF.
Meets EPA Tier II Emissions
EMCP III control panel, UL 508A Listed.
Skid mounted, with 3200 amp breakers.


Model 3516C Diesel Generator Set Rated 2000 kW, 480/277 Volt, 1800 RPM, 3 Phase, 60 Hertz, 4 Wire, 0.8 PF.

Meets EPA Tier II Emissions requirements for Non-Road Mobile


Standard Consist for 3516C Packaged Diesel Generator Set:

AIR INLET SYSTEM
Air Cleaner; single element canister type with service indicator

CONTROL PANELS
Control Panel
EMCP III control panel including:
24 Volt DC Control
NEMA 12, IP44 Dust Proof Enclosure
Lockable hinged door
Generator Terminal Box Mounted (rear facing)
UL 508A Listed
Panel illuminating lights
Auto start/stop control switch
Voltage adjustment potentiometer
True RMS AC metering, 3 phase
Digital indication for:
RPM
Operating hours
Oil pressure
Coolant temperature
DC Volts
L-L Volts, L-N Volts, Phase, Amps, Hz
ekW, kVa, kVAR, kWhr, % kW, PF
L/R Exhaust Manifold Temperature
Oil Temperature
Shutdowns with indicating lights for:
Low oil pressure
High coolant temperature
Overspeed
Emergency stop
Failure to start (overcrank)
Low coolant level
Oil Temperature
Programmable Protective Relaying Functions
Under and Over Voltage
Under and Over Frequency
Reverse Power
Over Current (Phase and Total)
3 Spare indicating LED's (Programmable)
4 Spare Alarm/Shutdown Inputs

COOLING SYSTEM
Separate Circuit After-Cooled
CVS Radiator sized for minimum 43C/110F @ 660 ft. at Standby rating
Radiator fan and fan drive
Fan and belt guards
Coolant drain line with valve
Coolant level sensors
Caterpillar Extended Life Coolant

EXHAUST SYSTEM
Dry Exhaust manifold
Flanged faced outlets

FUEL SYSTEM
Secondary fuel filters
Fuel cooler
Flexible fuel lines - shipped loose
Fuel priming pump

GENERATORS AND GENERATOR ATTACHMENTS
3 Phase Brushless, Salient Pole
Permanent Magnet Excited
6 lead
Permanent Magnet generators include Caterpillar's digital voltage regulator (CDVR). CDVR includes KVAR/PF modes, RFI suppression, min/max exciter limiter and exciter diode monitor.
Class F insulation, Class F temperature rise at 40C ambient = 130C
Reactive droop
Bus Bar connections
Winding Temperature detectors
Anti-condensation space heaters: 120/240 VAC, 1200 W

GOVERNING SYSTEM
Installed, ADEM II Governor

LUBE SYSTEM
Lubricating oil
Gear type lube oil pump
Integral lube oil cooler
Oil filter, filler and dipstick
Oil drain lines and valve
Fume disposal

MOUNTING SYSTEM
Rails - Engine/Generator/Radiator Mounting, 330 mm (13 in) structural steel rails
Spring-type anti-vibration mounts

STARTING/CHARGING SYSTEM
45 amp charging alternator
24 volt electric starting motors
Battery rack w/cables
Battery disconnect switch

GENERAL
PAINT, Caterpillar yellow; with high gloss black rails & radiator
RH Service
Flywheel and Flywheel housing-SAE No. 00
SAE Standard Rotation

The following accessories/services are also included:

Electronic Modular Control Panel 3.3
Provides all functions and indications of the EMCPII as well as direct Modus communication

Alarm Module, Installed in control panel, Provides the following additional alarms:
High Coolant Temperature Alarm
Low Coolant Temperature Alarm
Low Oil Pressure Alarm
Low DC Volts Alarm
System Not in Automatic Alarm
Low Fuel Level Alarm

Remote alarm annunciator, NFPA compliant:
Low Coolant Temperature Alarm
High Coolant Temperature Shutdown
Low Oil Pressure Shutdown
Overcrank
Overspeed Shutdown
Low Fuel Level Alarm
Generator On Load
Charger Malfunction

Remote alarm contacts:
Generator Ready
High Coolant Temperature, Pre-Alarm
Low Oil Pressure, Pre-Alarm
Low Coolant Temperature
Control Switch Not in Auto
Overcrank
Emergency Stop
High Coolant Temperature, Shutdown-Alarm
Low Oil Pressure, Shutdown-Alarm
Overspeed, Shutdown-Alarm
Fuel Tank Leak Alarm

Generator main line circuit breaker, 3200 Amp – 3 Phase – 480 Volt, Insulated Case.
DC Junction Box
AC Terminal Strip in Generator Housing
Generator Space Heater Relay

24 Volt Battery Set – 380 Ampere-hour, Battery Cables
Fiberglass battery rack/box
Jacket Water Heater – 240 VAC single phase, includes circulation pump
Battery Charger 10/2 Amp, 120 VAC input

Critical grade silencer, flexible fitting, elbow, rain cap


Fuel Priming Pump, RH
Fuel check valves
Fuel Cooler, installed on radiator
Flexible Fuel Lines, Installed

Oil Pan Drain Cover
Valved lube oil drain line.
Valved coolant drain line.
Lubricating Oil, Installed
Fumes Disposal line, vents crankcase to radiator exhaust stream
Antifreeze, Pre-mixed, Installed